电信科学 ›› 2024, Vol. 40 ›› Issue (3): 128-135.doi: 10.11959/j.issn.1000-0801.2024032

• 研究与开发 • 上一篇    

考虑系统运行方式的配电网分支线断线故障精确定位方法

徐飞, 邓言振, 刘宏辉, 汪辉, 赵海洋   

  1. 国网安徽省电力有限公司,安徽 合肥 230061
  • 修回日期:2024-02-20 出版日期:2024-03-01 发布日期:2024-03-01
  • 作者简介:徐飞(1985- ),男,国网安徽省电力有限公司高级工程师,主要研究方向为电网规划、建设、运检等
    邓言振(1991- ),男,国网安徽省电力有限公司工程师,主要研究方向为电网规划、前期、运检等
    刘宏辉(1991- ),男,国网安徽省电力有限公司工程师,主要研究方向为电网建设、运检、规划等
    汪辉(1989- ),男,国网安徽省电力有限公司工程师,主要研究方向为电网规划、建设、运检等
    赵海洋(1991- ),男,国网安徽省电力有限公司工程师,主要研究方向为电网规划、建设、运检等

Accurate location method of branch line break fault in distribution network considering system operation mode

Fei XU, Yanzhen DENG, Honghui LIU, Hui WANG, Haiyang ZHAO   

  1. State Grid Anhui Electric Power Co., Ltd., Hefei 230061, China
  • Revised:2024-02-20 Online:2024-03-01 Published:2024-03-01

摘要:

配电网分支线断线故障定位过程中,由于故障干扰分支节点识别方法的差异,难以确认断线发生范围,不同采样率下的故障定位结果相对误差较大。因此,提出考虑系统运行方式的配电网分支线断线故障精确定位方法。根据配电网的拓扑结构,分析供电系统内行波传输路径。基于供电系统运行方式,构建配电网分支节点连通矩阵,识别受到断线故障干扰的分支节点,确定断线发生范围,结合断线故障的特征参数,判断故障发生区段,结合零模和线模行波传播时间差,获取故障测距,实现配电网分支线断线故障精确定位。实例分析结果表明:获取精度较高的行波信号波形后,不同采样率下的故障定位结果相对误差降低了48%、12%。

关键词: 系统运行方式, 配电网, 断线故障, 精确定位, 受扰设备, 行波

Abstract:

In the process of locating faults caused by branch line breaks in distribution networks, it is difficult to determine the range of wire breakage due to differences in fault interference branch node identification methods.The relative error of fault location results under different sampling rates is relatively large.Therefore, a accurate location method for branch line break faults in distribution networks considering system operation mode was proposed.The traveling wave transmission path within the power supply system was analyzed based on the topology of the distribution network.A connection matrix for branch nodes was constructed in the distribution network based on the operating mode of the power supply system.Identify the branch nodes affected by wire breakage faults and determine the scope of wire breakage occurrence.Determine the fault occurrence interval based on the characteristic parameters of wire breakage faults.By combining the time difference between zero mode traveling wave and line mode traveling wave, fault location can be obtained, achieving precise positioning of branch line breakage faults in distribution networks.The example analysis results show that after obtaining a high-precision traveling wave signal waveform, the relative error of fault localization results at different sampling rates is reduced by 48% and 12%.

Key words: system operation mode, distribution network, break fault, accurate location, disturbed equipment, traveling wave

中图分类号: 

No Suggested Reading articles found!