Telecommunications Science ›› 2014, Vol. 30 ›› Issue (8): 106-111.doi: 10.3969/j.issn.1000-0801.2014.08.017
• Operating technology wide-angle • Previous Articles Next Articles
Yongshuang, Qiu Wenbo Lin,Yongshuang, Qiu Wenbo Lin
Online:
Published:
Abstract:
Beginning with Fourier Law and dealing with centralized and dispersive heat source in server with their merits, the architecture named parallel double-channels was proposed, which consist of “contact-type”and“non-contact-type”channels with significant difference on thermal resistance, and use the “heat pipe water cooling unit + cooling tower”contact-type-cooling-channel to remove the thermal current from the key-chips in server with high efficient. The verification experiment was organized,“the customized server with double-channels-cooling”was developed, and according to the experiment result, it is feasible to realize contact-type-cooling on the CPU in servers with natural cold source.
Key words: double-channels-cooling, heat pipe, water-cooling, internet data center, 45℃, server, CPU
Yongshuang, Qiu Wenbo Lin,Yongshuang, Qiu Wenbo Lin. Research and Experiment on Energy-Conservation Cooling Technique in IDC[J]. Telecommunications Science, 2014, 30(8): 106-111.